Same three-phase supply connected to loads in Star (Y) and Delta (Δ) configurations.
Side-by-side comparison of voltage relationships under both connections, verifying the \(\sqrt{3}\) proportionality.
\(V_{\text{line}} = \sqrt{3}\,V_{\text{phase}},\quad I_{\text{line}} = I_{\text{phase}}\)
\(V_{\text{line}} = V_{\text{phase}},\quad I_{\text{line}} = \sqrt{3}\,I_{\text{phase}}\)
Under the same supply, Δ-connected load phase voltage is \(\sqrt{3}\) times that of Y-connected load;
Δ-connected line current is 3 times that of Y-connected load.
Y-connection: load bears phase voltage, line voltage is \(\sqrt{3}\) times phase voltage (\(\approx 1.732\)).
Δ-connection: load bears line voltage (equal to phase voltage), line current is \(\sqrt{3}\) times phase current.
Under the same supply, Δ-connected load has higher voltage and larger current.
Y-connection is suitable for long-distance power distribution (with neutral point grounding); each phase load voltage is \(1/\sqrt{3}\) of the line voltage.
Δ-connection is suitable for high-power equipment such as motors, providing higher starting torque.
Total three-phase power is independent of connection type (for the same line voltage and line current).